SOUTH CABLE
RHW‑2 Copper Building Wire
Voltage:600V
Structure:ConductorBare copper per ASTM B3. Stranding is either Class B compressed per ASTM B8 or combination unilay per ASTM B787
InsulationCross Linked Polyethylene (XLPE) , Silicone-Free, Abrasion, High-Heat, Moisture Resistant
Insulation ColourBlack, Customized as needed


Overview Specifications FAQ Test&Acceptance Send Message

APPLICATION

Copper RHW-2 wire is a high-performance cable with annealed (soft) copper conductors for excellent electrical conductivity. Its insulation material is cross-linked polyethylene (XLPE), which has excellent heat and moisture resistance, and can operate in dry or humid environments with a maximum operating temperature of up to 90°C. The RHW-2 cable is rated for 600 volts.

CHARACTERISTICS

Voltage Rating Uo/U

600V

Temperature Rating

90°C dry or wet

STANDARDS

ASTM B3 Soft or Annealed Copper Wire

ASTM B8 Concentric-Lay-Stranded Copper Conductors

ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors

UL 44 Thermoset-Insulated Wires and Cables

CONSTRUCTION

Conductor

Bare copper per ASTM B3. Stranding is either Class B compressed per ASTM B8 or combination unilay per ASTM B787

Insulation

Cross Linked Polyethylene (XLPE) , Silicone-Free, Abrasion, High-Heat, Moisture Resistant

Insulation Colour

Black, Customized as needed

Cond. SizeStrand CountDiameter Over ConductorInsul. ThicknessApprox ODCopper WeightApprox Weight
AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
1470.07450.1611220
12Solid0.08450.1741928
1270.088450.1792028
1070.113450.2033242
870.141600.2599567
670.177600.381102
470.225600.345128153
370.252600.378162191
270.282600.403205244
1190.322800.481258304
1/0190.361800.522325390
2/0190.405800.564410481
3/0190.456800.616518598
4/0190.512800.672653742
250370.558950.748771884
300370.61950.8019261023
350370.661950.85110811213
400370.705950.89612351345
500370.789950.95615441696
600610.8651101.08518532028
750610.9681101.17123152492
1000611.1171101.33730883283


  • Who we are?

    SOUTH CABLE is a company specializing in the research, development, manufacturing,and sales of high-end wire and cable products.

  • How can we guarantee quality?

    Always a pre-production sample before mass production; Always final Inspection before shipment.

  • What can you buy from us?

    Wire, Cable


  • Why should you buy from us not from other suppliers?

    We have CSA and CUL certifications, We have Fifteen years of experience in design and development.

  • What services can we provide?

    Accepted Delivery Terms: FOB,CFR,CIF,EXW;
    Accepted Payment Currency:USD,EUR;
    Accepted Payment Type:T/T,L/C,Money Gram,Western Union;Language Spoken:English,Chinese,French


  • How long does it take to get a quote back

    Most quotes are returned within 24 hours

TEST

Tests are divided into routine tests, sampling tests and type test items.

1.Routine tests

routine tests: Tests carried out by the manufacturer on all manufactured lengths of finished cables toverify that all cables comply with specified requirements.Routine test items :Conductor resistance measurement, voltage test.

2.Sampling tests

Sampling tests: Tests carried out by the manufacturer on specimens of finished cables or on certaincomponents taken from finished cables at specified frequencies to check whether the cables complywith specified requirements.

Sampling test items:Conductor inspection, dimensional inspection,thermal extension testing ofinsulation and elastomer sheaths.

3.Type test

Type test:Tests carried out on normal commercial principles before supply of a type of cable covered by this standard to demonstrate that the cable has satisfactory performance under the conditions of intended use.

Type testing includes electrical type testing and non-electrical type testing items.

Electrical type test items:1) Insulation resistance measurement at ambient temperature.2) Measurement of insulation resistance at maximum conductor temperature during normal operation.3) 4h voltage test.

Non-electrical type test items include insulation non-electrical type test and sheath non-electrical type test.

Insulation non-electrical type test items: Dimensional measurements、mechanical properties(tensile strength and Elongation at break)、High temperature pressure test、Low temperature performance、Thermal shock test、Thermal extension test and water absorption test, etc.

Sheath non-electrical type test items:Dimensional measurements、mechanical properties(tensile strength and Elongation at break)、High temperature pressure test、Low temperature performance、Weight loss test and thermal shock test, etc.


Name: