| AC90 600V – 3 Aluminum Conductors | ||
| Voltage: | 600V | |
| Structure: | Conductor | Stranded AA-8000 Series Aluminum Alloy (ACM) |
| Insulation | Cross-linked Polyethylene (XLPE) CSA Type XL 90°C dry/wet 600V Halogen-Free | |
| Bonding Conductor | Stranded AA-8000 Series Aluminum Alloy (ACM) | |
| Armour | Aluminum (AIA) or Galvanized Steel (SIA) Interlock Armour | |
| Sheath Colour | 3 Core: Black White Red 4 Core: Black White Red and Blue | |
AC90 armoured building wire is rated FT4-ST1 for -40°C to 90°C. Engineered specifically for demanding environments, superior flammability and smoke emission performance. For use in ventilated, non-ventilated and ladder-type cable trays. For dry locations, in ceiling air-handling plenums, exposed or concealed wiring and service entrance above ground.
600V
-40°C to 90°C
Industry compliances: CSA Standard C22.2 No. 51, No.38 and No.2256, RoHS
Flame test compliances: CSA ST1 and FT4
Stranded AA-8000 Series Aluminum Alloy (ACM)
Cross-linked Polyethylene (XLPE) CSA Type XL 90°C dry/wet 600V Halogen-Free
Stranded AA-8000 Series Aluminum Alloy (ACM)
Aluminum (AIA) or Galvanized Steel (SIA) Interlock Armour
3 Core: Black White Red
4 Core: Black White Red and Blue
| CONDUCTOR SIZE | GROUND SIZE | INSULATION THICKNESS | CABLE DIAMETER | CABLE WEIGHT | MAX PULLING TENSION | MIN. BEND RADIUS | AMPACITY (A) |
| 6 AWG | 8 AWG | 0.045 in. | 0.800 in. | 243 lbs/Mft | 526 lbs | 11.2 in. | 55 |
| 1.14 mm | 20.3 mm | 361 kg/km | 239 kg | 285 mm | |||
| 4 AWG | 6 AWG | 0.045 in. | 0.880 in. | 286 lbs/Mft | 832 lbs | 12.3 in. | 75 |
| 1.14 mm | 22.4 mm | 426 kg/km | 377 kg | 313 mm | |||
| 2 AWG | 6 AWG | 0.045 in. | 1.030 in. | 392 lbs/Mft | 1322 lbs | 14.4 in. | 100 |
| 1.14 mm | 26.2 mm | 583 kg/km | 600 kg | 366 mm | |||
| 1 AWG | 4 AWG | 0.055 in. | 1.160 in. | 477 lbs/Mft | 1653 lbs | 16.2 in. | 115 |
| 1.40 mm | 29.5 mm | 710 kg/km | 750 kg | 413 mm | |||
| 1/0 AWG | 4 AWG | 0.055 in. | 1.250 in. | 622 lbs/Mft | 2081 lbs | 17.5 in. | 135 |
| 1.40 mm | 31.8 mm | 925 kg/km | 944 kg | 445 mm | |||
| 2/0 AWG | 4 AWG | 0.055 in. | 1.320 in. | 738 lbs/Mft | 2696 lbs | 18.5 in. | 150 |
| 1.40 mm | 33.5 mm | 1099 kg/km | 1223 kg | 469 mm | |||
| 3/0 AWG | 4 AWG | 0.055 in. | 1.420 in. | 843 lbs/Mft | 3375 lbs | 19.9 in. | 175 |
| 1.40 mm | 36.1 mm | 1254 kg/km | 1531 kg | 505 mm | |||
| 4/0 AWG | 4 AWG | 0.055 in. | 1.530 in. | 994 lbs/Mft | 4199 lbs | 21.4 in. | 205 |
| 1.40 mm | 38.9 mm | 1479 kg/km | 1905 kg | 544 mm | |||
| 250 kcmil | 2 AWG | 0.065 in. | 1.641 in. | 1203 lbs/Mft | 5152 lbs | 23.0 in. | 230 |
| 1.65 mm | 41.7 mm | 1791 kg/km | 2337 kg | 584 mm | |||
| 300 kcmil | 2 AWG | 0.065 in. | 1.828 in. | 1355 lbs/Mft | 5807 lbs | 25.6 in. | 260 |
| 1.65 mm | 46.4 mm | 2017 kg/km | 2634 kg | 650 mm | |||
| 350 kcmil | 2 AWG | 0.065 in. | 1.843 in. | 1546 lbs/Mft | 7396 lbs | 25.8 in. | 280 |
| 1.65 mm | 46.8 mm | 2301 kg/km | 3355 kg | 655 mm | |||
| 400 kcmil | 2 AWG | 0.065 in. | 1.991 in. | 1713 lbs/Mft | 7960 lbs | 27.9 in. | 305 |
| 1.65 mm | 50.6 mm | 2549 kg/km | 3611 kg | 708 mm | |||
| 500 kcmil | 1 AWG | 0.080 in. | 2.155 in. | 2112 lbs/Mft | 9804 lbs | 30.2 in. | 350 |
| 2.03 mm | 54.7 mm | 3143 kg/km | 4447 kg | 766 mm | |||
| 600 kcmil | 1 AWG | 0.080 in. | 2.320 in. | 2447 lbs/Mft | 12103 lbs | 32.5 in. | 385 |
| 2.03 mm | 59 mm | 3642 kg/km | 5490 kg | 825 mm | |||
| 750 kcmil | 1/0 AWG | 0.080 in. | 2.523 in. | 2934 lbs/Mft | 15568 lbs | 35.3 in. | 435 |
| 2.03 mm | 64.1 m | 4367 kg/km | 7062 kg | 897 mm |
SOUTH CABLE is a company specializing in the research, development, manufacturing,and sales of high-end wire and cable products.
Always a pre-production sample before mass production; Always final Inspection before shipment.
Wire, Cable
We have CSA and CUL certifications, We have Fifteen years of experience in design and development.
Accepted Delivery Terms: FOB,CFR,CIF,EXW;
Accepted Payment Currency:USD,EUR;
Accepted Payment Type:T/T,L/C,Money Gram,Western Union;Language Spoken:English,Chinese,French
Most quotes are returned within 24 hours
TEST
Tests are divided into routine tests, sampling tests and type test items.
routine tests: Tests carried out by the manufacturer on all manufactured lengths of finished cables toverify that all cables comply with specified requirements.Routine test items :Conductor resistance measurement, voltage test.
Sampling tests: Tests carried out by the manufacturer on specimens of finished cables or on certaincomponents taken from finished cables at specified frequencies to check whether the cables complywith specified requirements.
Sampling test items:Conductor inspection, dimensional inspection,thermal extension testing ofinsulation and elastomer sheaths.
Type test:Tests carried out on normal commercial principles before supply of a type of cable covered by this standard to demonstrate that the cable has satisfactory performance under the conditions of intended use.
Type testing includes electrical type testing and non-electrical type testing items.
Electrical type test items:1) Insulation resistance measurement at ambient temperature.2) Measurement of insulation resistance at maximum conductor temperature during normal operation.3) 4h voltage test.
Non-electrical type test items include insulation non-electrical type test and sheath non-electrical type test.
Insulation non-electrical type test items: Dimensional measurements、mechanical properties(tensile strength and Elongation at break)、High temperature pressure test、Low temperature performance、Thermal shock test、Thermal extension test and water absorption test, etc.
Sheath non-electrical type test items:Dimensional measurements、mechanical properties(tensile strength and Elongation at break)、High temperature pressure test、Low temperature performance、Weight loss test and thermal shock test, etc.